In order to achieve energy efficient operation of chiller plant, a computer based supervisory controller is utilized. This controller receives input Data from sensors located in pipe lines and outside. Supply and Return Temperatures, pipe line pressures and chilled water flow rates are available. This data is utilized by the controller for calculating actual cooling demand in the building, and for sequencing of the plant. Plant includes all chillers, boilers, chilled/hot water pumps, condenser water pumps, cooling tower fans and variable frequency drives.
Following sequence may be used for highest energy efficiency.
1) Set point temperature for chilled water is entered to the controller. When temperature is higher than set point, chiller plant is started.
2) Integrated Part Load Values for equipment are determined and data of energy consumption at part loads for each machine is fed to the controller. Building actual cooling demand at any part load condition is calculated by the controller by taking flow reading and chilled water delta t. Controller decides which set of equipment will provide best performance at any load condition. These equipment are brought in to the circuit
3) Leaving chilled water temperature at the chiller is very critical parameter as for as energy consumption is concerned. When chiller is required to produce chilled water at lower temperatures, it consumes more energy. At higher chilled water out temperatures, chiller energy consumption is substantially low. Why temperature is set at higher level or lower level depends upon cooling conditions required. At any stage controller analyses required cooling capacity with optimum chilled water out temperature which is most energy efficient. Chiller is operated at this temperature out condition.
4) Chiller operating efficiency depends on condenser water inlet temperature. Condenser water is cooled at cooling tower. This temperature may be controlled by,
a) Modulating speed of cooling tower fan
b) Flow of water to the towers.
Ambient wet bulb temperature determines up to what condition cooling water may be cooled. Cooling tower water temperature is adjusted by the controller to get maximum efficiency by the chiller. Inlet conditions are varied in different seasons to get better operating conditions.
5) Chilled water is circulated throughout the building by pumps. These pumps consume lot of energy. As cooling demand is not constant in the building, water flow rate to the building is varied accordingly. Variable Frequency Drives on the pump motor modulates its speed. Consequently energy consumed at part loads is lower as compared to peak demand. This step saves energy wastage.
Leave a comment
« EFFICIENCY IMPROVEMENT AND OPERATING COST REDUCTION BY BUILDING BMS SYSTEM
Recent Posts
- OPTIMUM CHILLER PLANT SEQUENCE OF OPERATION
- EFFICIENCY IMPROVEMENT AND OPERATING COST REDUCTION BY BUILDING BMS SYSTEM
- Salient Features of Energy Efficient Homes
- Interesting story idea for your readers
- Coordinated Practices for Green Building Design
- Use of Thermal Images for Indoor Environmental Control
- Absorption Chiller Suppliers
- Improving Efficiency of Existing Data Centers
- Electric Chiller Suppliers
- HVAC ENGINEER
- HVAC ENGINEER
- ENERGY EFFICIENT OPERATION OF COOLING TOWERS
- Salient Features of Healthcare AHU
- Multipurpose Hall Environment Control
- Piping Network Considerations for Air Conditioning System
Categories
- Absorption Chiller Suppliers
- AHU Coils
- Air Conditioning Systems
- Air Distribution
- Air Filtration
- Air Handling Units
- Building Management System
- Chilled Water Plant ΔT
- Chiller Plant Control Sequence
- Chillers
- Combined Cooling Heating & Power Systems
- Cooling Towers
- Cost Effective and Energy Efficient Air Side Economizer Systems
- Data Center Air Conditioning
- Demand Control Ventilation
- Displacement Ventilation Systems
- Ducting System
- ELECTRIC CHILLER SUPPLIERS
- Energy Efficient Pumping
- Energy Recoveries
- Fans For High Performing HVAC
- Green Building Design
- Green Solution
- Hospital HVAC
- How to Control Low Chilled Water delta-T
- HVAC ENGINEERS
- Indoor Air Quality
- Insulations
- Kitchen Ventilation
- Night Time Precooling
- Noise Control
- Optimized Chiller Operation
- Pumping Solutions
- Refrigerant Pipng
- Smoke Management Systems
- Solar Energy Systems
- Thermal Energy Storage for Cooling
- Variable Frequency Drives
- Variable-Flow Pumping Systems
Archives
| M | T | W | T | F | S | S |
|---|---|---|---|---|---|---|
| « Dec | ||||||
| 1 | ||||||
| 2 | 3 | 4 | 5 | 6 | 7 | 8 |
| 9 | 10 | 11 | 12 | 13 | 14 | 15 |
| 16 | 17 | 18 | 19 | 20 | 21 | 22 |
| 23 | 24 | 25 | 26 | 27 | 28 | 29 |
| 30 | ||||||
Recent Comments
- HAVC Units on How to Achieve Low Humidity Conditions with Minimum Energy Consumption
- dentist on Identifying Objectionable Noise Sources in Air Conditioning Systems
- ideas for window treatments for bay windows on High Performance Strategies for Solar Protection
- Bidet toilet seat on Best Location to Introduce Makeup Air in Commercial Kitchen
- face exercises on Using Fiberglass Duct liner for Air Conditioning System Noise Mitigation
Meta
- Log in
- Entries RSS
- Comments RSS
- WordPress.org